Discuss a project

6–10kVMedium voltage

KSO-298 and KSO-292 cubicles, K-59, K-104, K-37 and K-6-U switchgear cabinets, YaKNO cells, packaged transformer substations — own manufacturing, installation and commissioning.

Front of a KSO-298 cubicle: relay compartment, disconnector drives

Applications

  • Distribution substations
  • Transformer substations
  • Power supply of industrial enterprises

Equipment

  • Prefabricated single-sided service cubicles

    Request a quote
    KSO-298: Prefabricated single-sided service cubicles — renderingRendering
    KSO-298 in the BIONIKA workshop — photo 1
    KSO-298 in the BIONIKA workshop — photo 2
    KSO-298 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    KSO-298

    Prefabricated single-sided service cubicles

    Single-sided service cubicles for 6–10 kV switchgear: installed in a row against a wall, with drives and relay equipment on the front. The cubicles take vacuum circuit breakers, load-break switches or disconnectors with earthing switches, depending on the connection scheme. In the photo: assembled rows of KSO cubicles in the BIONIKA workshop — relay compartments, drives, busbars behind a mesh guard.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    400; 630; 1000 A
    Rated busbar current
    630; 1000 A
    Thermal withstand current
    20 kA (3 s)
    Peak withstand current
    51 kA
    Switching devices
    vacuum circuit breaker, load-break switch, disconnector
    Design
    indoor installation, U3; single-sided service
  • Prefabricated single-sided service cubicles

    Request a quote
    KSO-292: Prefabricated single-sided service cubicles — renderingRendering
    KSO-292 in the BIONIKA workshop — photo 1
    KSO-292 in the BIONIKA workshop — photo 2
    KSO-292 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    KSO-292

    Prefabricated single-sided service cubicles

    Cubicles for 6–10 kV distribution and transformer substations in networks with an isolated neutral or a neutral earthed through a reactor. Inside: a relay compartment with protection and metering devices; on the front: drives of load-break switches and disconnectors; the busbars are behind a mesh guard.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    400; 630 A
    Rated busbar current
    630; 1000 A
    Rated breaking current
    20 kA
    Switching devices
    vacuum circuit breaker, load-break switch, RVZ / RVFZ disconnectors
    Design
    indoor installation, U3; single-sided service
  • Prefabricated single-sided service cubicles

    Request a quote
    KSO-285: Prefabricated single-sided service cubicles — renderingRendering
    KSO-285 in the BIONIKA workshop — photo 1
    KSO-285 in the BIONIKA workshop — photo 2
    KSO-285 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    KSO-285

    Prefabricated single-sided service cubicles

    Cubicles for 6–10 kV switchgear of urban and industrial substations, distribution substations and electric transport networks. Fitted with vacuum circuit breakers with spring-motor drives; protection on electromechanical relays or microprocessor units. In the photo: switchgear at a customer’s site — a row of KSO cubicles with relay compartments, drives and busbars behind a mesh guard, and a voltage transformer cubicle.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    400; 630; 1000 A
    Rated busbar current
    630; 1000 A
    Thermal withstand current
    20 kA (3 s)
    Peak withstand current
    51 kA
    Switching devices
    vacuum circuit breaker with a spring-motor drive
    Design
    indoor installation; single-sided service
  • Metal-clad switchgear (KRU) cabinets

    Request a quote
    K-59: Metal-clad switchgear (KRU) cabinets — renderingRendering
    K-59 in the BIONIKA workshop — photo 1
    K-59 in the BIONIKA workshop — photo 2
    K-59 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    K-59

    Metal-clad switchgear (KRU) cabinets

    6–10 kV switchgear cabinets with a withdrawable unit: the circuit breaker sits on a truck and is rolled out for service; the breaker, busbar, cable and relay compartments are separated. The series is made for indoor installation and as part of KRUN outdoor switchgear. In the photo: a relay compartment with protection devices and a cabinet with the breaker on its truck.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    630–3150 A
    Rated breaking current
    20; 31.5 kA
    Thermal withstand current
    20; 31.5 kA (3 s)
    Peak withstand current
    51; 81 kA
    Circuit breaker type
    vacuum, on a withdrawable truck
    Design
    indoor installation or as part of a KRUN
  • Metal-clad switchgear (KRU) cabinets

    Request a quote
    K-104: Metal-clad switchgear (KRU) cabinets — renderingRendering
    K-104 in the BIONIKA workshop — photo 1
    K-104 in the BIONIKA workshop — photo 2
    K-104 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    K-104

    Metal-clad switchgear (KRU) cabinets

    Indoor 6–10 kV switchgear cabinets with a withdrawable unit: a vacuum circuit breaker on a truck, a relay cabinet with microprocessor protection, shutters that close the contacts automatically when the truck is withdrawn. Used in switchgear of substations, power plants and industrial enterprises.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    630–3150 A
    Rated breaking current
    20; 25; 31.5 kA
    Thermal withstand current
    20–31.5 kA (3 s)
    Peak withstand current
    51–81 kA
    Circuit breaker type
    vacuum, on a withdrawable truck
    Design
    indoor installation, U3; two-sided service
  • Metal-clad switchgear with a vacuum circuit breaker

    Request a quote
    K-37: Metal-clad switchgear with a vacuum circuit breaker — renderingRendering
    K-37 in the BIONIKA workshop — photo 1
    K-37 in the BIONIKA workshop — photo 2
    K-37 in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    K-37

    Metal-clad switchgear with a vacuum circuit breaker

    Outdoor 6–10 kV KRUN cabinets with a withdrawable vacuum circuit breaker and a relay protection and control cabinet. The cabinets make up incomers, outgoing lines, bus sectioning, VT and auxiliary transformer cabinets.

    Rated voltage
    6; 10 kV (highest operating voltage 7.2; 12 kV)
    Rated current of main circuits
    630; 1000; 1600 A
    Rated breaking current
    20; 31.5 kA
    Thermal withstand current
    20; 31.5 kA
    Peak withstand current
    51; 81 kA
    Circuit breaker type
    vacuum, on a withdrawable truck
    Design
    outdoor installation, U1 or UKhL1
  • K-6-U: Metal-clad switchgear cabinets — renderingRendering
    K-6-U in the BIONIKA workshop — photo 1
    K-6-U in the BIONIKA workshop — photo 2
    K-6-U in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6–10 kV

    K-6-U

    Metal-clad switchgear cabinets

    Steel-enclosed cabinets with compartments for high-voltage equipment.

  • Free-standing outdoor quarry cell

    Request a quote
    YaKNO: Free-standing outdoor quarry cell — renderingRendering
    YaKNO in the BIONIKA workshop — photo 1
    YaKNO in the BIONIKA workshop — photo 2
    YaKNO in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6; 10 kV

    YaKNO

    Free-standing outdoor quarry cell

    Outdoor 6–10 kV cells for quarries and open-pit mining: they supply excavators, drilling rigs and other mobile machinery and section quarry lines. The enclosure is protected against dust, moisture and mechanical damage.

    Rated voltage
    6; 10 kV
    Design
    outdoor, free-standing
  • KTP: Packaged transformer substations
    KTP in the BIONIKA workshop — photo 1
    KTP in the BIONIKA workshop — photo 2
    KTP in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6(10)/0.4 kV

    KTP

    Packaged transformer substations

    Packaged 6(10)/0.4 kV transformer substations: the high-voltage section, power transformer and 0.4 kV distribution board in one factory-built enclosure. Made in the workshop and installed on site.

    Transformer rating
    25–2500 kVA
    HV / LV voltage
    6 or 10 / 0.4 kV
    Scheme
    dead-end or pass-through; one or two transformers
    Design
    outdoor (U1) or indoor installation
  • Urban packaged transformer substation

    Request a quote
    GKTP: Urban packaged transformer substation — renderingRendering
    GKTP in the BIONIKA workshop — photo 1
    GKTP in the BIONIKA workshop — photo 2
    GKTP in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6(10)/0.4 kV

    GKTP

    Urban packaged transformer substation

    Urban packaged transformer substations 6(10)/0.4 kV in a steel enclosure on a foundation: they supply residential buildings, public buildings and small businesses. Inside: a high-voltage compartment, a power transformer and a 0.4 kV board with outgoing lines.

    Transformer rating
    25–1000 kVA
    HV / LV voltage
    6 or 10 / 0.4 kV
    Scheme
    dead-end or pass-through, one transformer
    Design
    outdoor installation, U1; cable entries
  • Double urban packaged transformer substation

    Request a quote
    2GKTP: Double urban packaged transformer substation — renderingRendering
    2GKTP in the BIONIKA workshop — photo 1
    2GKTP in the BIONIKA workshop — photo 2
    2GKTP in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    6(10)/0.4 kV

    2GKTP

    Double urban packaged transformer substation

    Urban 6(10)/0.4 kV substations with two power transformers in a steel enclosure: if one transformer fails, the other takes the load. For consumers who need a backup supply: residential complexes, hospitals, retail and public buildings.

    Transformer ratings
    2 × 250–1000 kVA
    HV / LV voltage
    6 or 10 / 0.4 kV
    Scheme
    dead-end or pass-through; two 0.4 kV bus sections
    Design
    outdoor installation, U1; cable entries
  • Pole-mounted packaged transformer substation

    Request a quote
    KTPS: Pole-mounted packaged transformer substation — renderingRendering

    6(10)/0.4 kV

    KTPS

    Pole-mounted packaged transformer substation

    Compact outdoor substation for 6–10 kV overhead lines: a high-voltage entry with arresters, a power transformer and a 0.4 kV cabinet in one unit. Supplies villages, farms, pumping stations, construction sites and small production facilities.

    Transformer rating
    25–250 kVA
    HV / LV voltage
    6 or 10 / 0.4 kV
    Scheme
    dead-end, HV overhead entry
    Design
    outdoor installation, U1
  • Reactive power compensation units

    Request a quote
    UKRM: Reactive power compensation units — renderingRendering
    UKRM in the BIONIKA workshop — photo 1
    UKRM in the BIONIKA workshop — photo 2
    UKRM in the BIONIKA workshop — photo 3

    Photos from the BIONIKA workshop

    0.4–0.69 kV and 6–10 kV

    UKRM

    Reactive power compensation units

    Capacitor banks for reactive power compensation in 0.4–0.69 kV and 6–10 kV networks. NOVAR / DCRL / DCRG controllers automatically switch the number of connected capacitors and keep cos φ constant: fewer penalties from the power supply company and higher load capacity of lines and transformers.

    Network voltage
    400 / 440 / 525 / 690 V; 6 and 10 kV
    Controllers
    NOVAR / DCRL / DCRG
    Rating
    calculated for the site; typical range from 10 to 1000 kvar and above
    Design
    indoor (U3) or outdoor (U1) installation

Technical capabilities

Voltage classes
6 kV, 10 kV
Completed
50+ sites
Types of work
Manufacturing, installation, commissioning, testing
Permits
Permits and licences for work in power networks from 0.4 to 500 kV

Technical documentation

  • Questionnairein preparation
  • Technical cataloguein preparation
  • Standard diagramsin preparation

A 6–10 kV project?

Send us the technical specification — BIONIKA specialists will assess the project and propose a solution.